Utility Collar

The Snap Utility Collar is a versatile continuous stainless-steel strip that can be cut to size to provide over 500 applications for slabs and walls.

Refer to the Data Sheet for the following:

  • Collar Segment and No. of Brackets
  • Fixing Requirements
  • Maximum Hole Size
  • Sealant Requirements

The allowable installations (refer to the tables below) can be found in FCO3520. The report also includes allowable variations covering:

  • Painting on the collar body, though no paint is allowed on the active area of the collar (Section 3.3)
  • 40mm min. spacing from outer edge of collar to outer edge of collar (Section 3.3)

Click here for Assessment Report FCO3520

Click here for Data Sheet

Click here for Installation Instructions

SKU: N/A Categories: ,

Documentation

Concrete or Bondek Slab - Stack Applications (see Note 1)

Pipe Dia.
(nom mm)
FittingCollarFRL - Slab Thickness
≥120mm≥150mm≥175mm

PVC Pipes in Concrete or Bondek Slabs

40NoUtility 40-/120/120-/180/180-/240/240
40YesUtility 40+-/120/120-/180/180-/240/240
50NoUtility 50-/120/120-/180/180-/240/240
50YesUtility 50+-/120/120-/180/180-/240/240
65NoUtility 65-/120/120-/180/180-/240/240
65YesUtility 65+-/120/120-/180/180-/240/240
80NoUtility 80-/120/120-/180/180-/240/240
80YesUtility 80+-/120/120-/180/180-/240/240
90NoUtility 80+-/120/120-/180/180-/240/240
90YesUtility 90+-/120/120-/180/180-/240/240
100NoUtility 100-/120/120-/180/180-/240/240
100YesUtility 100+-/120/120-/180/180-/240/240
150NoUtility 150n/a-/180/180-/240/240

HDPE Pipes in Concrete or Bondek Slabs

40NoUtility 40-/120/120-/180/180-/240/240
50NoUtility 50-/120/120-/180/180-/240/240
56NoUtility 50-/120/120-/180/180-/240/240
63NoUtility 50+-/120/120-/180/180-/240/240
75NoUtility 65+-/120/120-/180/180-/240/240
90NoUtility 80+-/120/120-/180/180-/240/240
110NoUtility 100-/120/120-/180/180-/240/240
160NoUtility 150n/a-/180/180-/240/240

Triplus Pipes in Concrete or Bondek Slabs

40NoUtility 40-/120/120-/180/180-/240/240
50NoUtility 50-/120/120-/180/180-/240/240
75NoUtility 65+-/120/120-/180/180-/240/240
90NoUtility 80+-/120/120-/180/180-/240/240
110NoUtility 100-/120/120-/180/180-/240/240
160NoUtility 150n/a-/180/180-/240/240

Raupiano Pipes in Concrete or Bondek Slabs

40NoUtility 40-/120/120-/180/180-/240/240
50NoUtility 50-/120/120-/180/180-/240/240
75NoUtility 65+-/120/120-/180/180-/240/240
110NoUtility 100-/120/120-/180/180-/240/240
160NoUtility 150n/a-/180/180-/240/240
Note 1: Fullers Firesound to fill Bondek channel underneath collar and 20mm beyond collar (Figure 4 FCO3520).

Back to top

Plasterboard Lined Steel Stud Walls

Pipe Dia.
(nom mm)
FittingCollarFRL - Wall Lining
≥1x13mm Sheets≥2x13mm Sheets

PVC Pipes in Plasterboard Lined Steel Stud Walls

40NoUtility 40-/60/60-/120/120
40YesUtility 40+-/60/60-/120/120
50NoUtility 50-/60/60-/120/120
50YesUtility 50+-/60/60-/120/120
65NoUtility 65-/60/60-/120/120
65YesUtility 65+-/60/60-/120/120
80NoUtility 80-/60/60-/120/120
80YesUtility 80+-/60/60-/120/120
90NoUtility 80+-/60/60-/120/120
90YesUtility 90+-/60/60-/120/120
100NoUtility 100-/60/60-/120/120
100YesUtility 100+-/60/60-/120/120
150NoUtility 150-/60/60-/120/120

HDPE Pipes in Plasterboard Lined Steel Stud Walls

40NoUtility 40-/60/60-/120/120
50NoUtility 50-/60/60-/120/120
56NoUtility 50-/60/60-/120/120
63NoUtility 50+-/60/60-/120/120
75NoUtility 65+-/60/60-/120/120
90NoUtility 80+-/60/60-/120/120
110NoUtility 100-/60/60-/120/120
160NoUtility 150n/a-/120/90

Triplus Pipes in Plasterboard Lined Steel Stud Walls

40NoUtility 40-/60/60-/120/120
50NoUtility 50-/60/60-/120/120
75NoUtility 65+-/60/60-/120/120
90NoUtility 80+-/60/60-/120/120
110NoUtility 100-/60/60-/120/120
160NoUtility 150-/60/60-/120/120

Raupiano Pipes in Plasterboard Lined Steel Stud Walls

40NoUtility 40-/60/60-/120/120
50NoUtility 50-/60/60-/120/120
75NoUtility 65+-/60/60-/120/120
110NoUtility 100-/60/60-/120/120
160NoUtility 150-/60/60-/120/120

Back to top

Masonry Walls (see Note 2)

Pipe Dia.
(nom mm)
FittingCollarFRL - Wall Thickness
≥90mm≥116mm

PVC Pipes in Masonry Walls

40NoUtility 40-/60/60-/120/120
40YesUtility 40+-/60/60-/120/120
50NoUtility 50-/60/60-/120/120
50YesUtility 50+-/60/60-/120/120
65NoUtility 65-/60/60-/120/120
65YesUtility 65+-/60/60-/120/120
80NoUtility 80-/60/60-/120/120
80YesUtility 80+-/60/60-/120/120
90NoUtility 80+-/60/60-/120/120
90YesUtility 90+-/60/60-/120/120
100NoUtility 100-/60/60-/120/120
100YesUtility 100+-/60/60-/120/120
150NoUtility 150n/a-/120/120

HDPE Pipes in Masonry Walls

40NoUtility 40-/60/60-/120/120
50NoUtility 50-/60/60-/120/120
56NoUtility 50-/60/60-/120/120
63NoUtility 50+-/60/60-/120/120
75NoUtility 65+-/60/60-/120/120
90NoUtility 80+-/60/60-/120/120
110NoUtility 100-/60/60-/120/120
160NoUtility 150n/a-/120/90

Triplus Pipes in Masonry Walls

40NoUtility 40-/60/60-/120/120
50NoUtility 50-/60/60-/120/120
75NoUtility 65+-/60/60-/120/120
90NoUtility 80+-/60/60-/120/120
110NoUtility 100-/60/60-/120/120
160NoUtility 150-/60/60-/120/120

Raupiano Pipes in Masonry Walls

40NoUtility 40-/60/60-/120/120
50NoUtility 50-/60/60-/120/120
75NoUtility 65+-/60/60-/120/120
110NoUtility 100-/60/60-/120/120
160NoUtility 150-/60/60-/120/120
Note 2: All Fire Resistance Levels (FRLs) achieved on framed plasterboard wall systems are applicable to concrete or masonry walls of equal or greater thickness (AS1530.4: 2014 Section 10.12.2 (c)).

Back to top

Hebel Walls (see Note 2)

Pipe Dia.
(nom mm)
FittingCollarFRL - Hebel Panel
75mm
(single mesh)
75mm
(caged mesh)

PVC Pipes in Hebel Walls

40NoUtility 40-/90/90-/120/120
40YesUtility 40+-/90/90-/120/120
50NoUtility 50-/90/90-/120/120
50YesUtility 50+-/90/90-/120/120
65NoUtility 65-/90/90-/120/120
65YesUtility 65+-/90/90-/120/120
80NoUtility 80-/90/90-/120/120
80YesUtility 80+-/90/90-/120/120
90NoUtility 80+-/90/90-/120/120
90YesUtility 90+-/90/90-/120/120
100NoUtility 100-/90/90-/120/120
100YesUtility 100+-/90/90-/120/120
150NoUtility 150-/90/90-/120/90

HDPE Pipes in Hebel Walls

40NoUtility 40-/90/90-/120/120
50NoUtility 50-/90/90-/120/120
56NoUtility 50-/90/90-/120/120
63NoUtility 50+-/90/90-/120/120
75NoUtility 65+-/90/90-/120/120
90NoUtility 80+-/90/90-/120/120
110NoUtility 100-/90/90-/120/120
160NoUtility 150-/90/60-/120/90

Triplus Pipes in Hebel Walls

40NoUtility 40-/90/90-/120/120
50NoUtility 50-/90/90-/120/120
75NoUtility 65+-/90/90-/120/120
90NoUtility 80+-/90/90-/120/120
110NoUtility 100-/90/90-/120/120
160NoUtility 150-/90/90-/120/120

Raupiano Pipes in Hebel Walls

40NoUtility 40-/90/90-/120/120
50NoUtility 50-/90/90-/120/120
75NoUtility 65+-/90/90-/120/120
110NoUtility 100-/90/90-/120/120
160NoUtility 150-/90/90-/120/120

Back to top

PVC Pipes in Dincel Wall, AFS Logicwall or AFS Rediwall (see Note 3)

Pipe Dia.
(nom mm)
FittingCollarFRL - Wall Type
110mm
Dincel
110mm
Rediwall
120mm
Logicwall LW120
155mm
Dincel

PVC Pipes in Dincel Wall, AFS Logicwall or AFS Rediwall

40NoUtility 40-/90/90-/90/90-/120/120-/180/180
40YesUtility 40+-/90/90-/90/90-/120/120-/180/180
50NoUtility 50-/90/90-/90/90-/120/120-/180/180
50YesUtility 50+-/90/90-/90/90-/120/120-/180/120
65NoUtility 65-/90/90-/90/90-/120/120-/180/180
65YesUtility 65+-/90/90-/90/90-/120/120-/180/120
80NoUtility 80-/90/90-/90/90-/120/120-/180/180
80YesUtility 80+-/90/90-/90/90-/120/120-/180/120
90NoUtility 80+-/90/90-/90/90-/120/120-/180/180
90YesUtility 90+-/90/90-/90/90-/120/120-/180/120
100NoUtility 100-/90/90-/90/90-/120/120-/180/180
100YesUtility 100+-/90/90-/90/90-/120/120-/180/120
150NoUtility 150-/90/90-/90/90-/120/120-/180/120

HDPE Pipes in Dincel Wall, AFS Logicwall or AFS Rediwall

40NoUtility 40-/90/90-/90/90-/120/120-/180/120
50NoUtility 50-/90/90-/90/90-/120/120-/180/120
56NoUtility 50-/90/90-/90/90-/120/120-/180/120
63NoUtility 50+-/90/90-/90/90-/120/120-/180/120
75NoUtility 65+-/90/90-/90/90-/120/120-/180/120
90NoUtility 80+-/90/90-/90/90-/120/120-/180/120
110NoUtility 100-/90/90-/90/90-/120/120-/180/120
160NoUtility 150-/90/90-/90/90-/120/90-/180/90

Triplus Pipes in Dincel Wall, AFS Logicwall or AFS Rediwall

40NoUtility 40-/90/90-/90/90-/120/120-/180/120
50NoUtility 50-/90/90-/90/90-/120/120-/180/120
75NoUtility 65+-/90/90-/90/90-/120/120-/180/120
90NoUtility 80+-/90/90-/90/90-/120/120-/180/120
110NoUtility 100-/90/90-/90/90-/120/120-/180/120
160NoUtility 150-/90/90-/90/90-/120/120-/180/120

Raupiano Pipes in Dincel Wall, AFS Logicwall or AFS Rediwall

40NoUtility 40-/90/90-/90/90-/120/120-/180/180
50NoUtility 50-/90/90-/90/90-/120/120-/180/180
75NoUtility 65+-/90/90-/90/90-/120/120-/180/180
110NoUtility 100-/90/90-/90/90-/120/120-/180/180
160NoUtility 150-/90/90-/90/90-/120/120-/180/180
Note 3: Fixings to be away from void with a minimum of 25mm embedment into concrete part of the wall.

Back to top

Speedpanel Walls (see Note 4)

Pipe Dia.
(nom mm)
FittingCollarFRL - Plasterboard Patching
1 x min.
13mm FR
1 x min.
16mm FR
2 x min.
13mm FR

PVC Pipes in Speedpanel walls

40NoUtility 40-/60/60-/90/90-/120/120
40YesUtility 40+-/60/60-/90/90-/120/120
50NoUtility 50-/60/60-/90/90-/120/120
50YesUtility 50+-/60/60-/90/90-/120/120
65NoUtility 65-/60/60-/90/90-/120/120
65YesUtility 65+-/60/60-/90/90-/120/120
80NoUtility 80-/60/60-/90/90-/120/120
80YesUtility 80+-/60/60-/90/90-/120/120
90NoUtility 80+-/60/60-/90/90-/120/120
90YesUtility 90+-/60/60-/90/90-/120/120
100NoUtility 100-/60/60-/90/90-/120/120
100YesUtility 100+-/60/60-/90/90-/120/120
150NoUtility 150-/60/60-/90/90-/120/120

HDPE Pipes in Speedpanel walls

40NoUtility 40-/60/60-/90/90-/120/120
50NoUtility 50-/60/60-/90/90-/120/120
56NoUtility 50-/60/60-/90/90-/120/120
63NoUtility 50+-/60/60-/90/90-/120/120
75NoUtility 65+-/60/60-/90/90-/120/120
90NoUtility 80+-/60/60-/90/90-/120/120
110NoUtility 100-/60/60-/90/90-/120/120
160NoUtility 150-/60/60-/90/90-/120/90

Triplus Pipes in Speedpanel walls

40NoUtility 40-/60/60-/90/90-/120/120
50NoUtility 50-/60/60-/90/90-/120/120
75NoUtility 65+-/60/60-/90/90-/120/120
90NoUtility 80+-/60/60-/90/90-/120/120
110NoUtility 100-/60/60-/90/90-/120/120
160NoUtility 150-/60/60-/90/90-/120/120

Raupiano Pipes in Speedpanel walls

40NoUtility 40-/60/60-/90/90-/120/120
50NoUtility 50-/60/60-/90/90-/120/120
75NoUtility 65+-/60/60-/90/90-/120/120
110NoUtility 100-/60/60-/90/90-/120/120
160NoUtility 150-/60/60-/90/90-/120/120
Note 4: Patching to be 250mm x 250mm plasterboard fixed to wall with 14g-10 65mm hex-head screws at maximum 100mm centres.

Back to top

Product Specs

Element

, , , , , , ,

Cast-In or Retrofit

Application

,

Pipe Type

, , , ,

Tested Systems

Stack Applications Dia.Collar SizeFRLReport No.
120mm+ Concrete Slab
PVC (SC) Pipe100Utility 100-/240/120FSP2333
- w Fitting Inside Collar100Utility 100+-/240/120FSP2333
- w Fitting Inside Collar100Utility 100+-/240/120FSP2358
- w Fitting Inside Collar100Utility 100+-/240/120FSP2371
PVC Pipe80Utility 80-/240/120FSP2358
PVC Pipe65Utility 65-/240/120FSP2358
PVC Pipe50Utility 50-/240/120FSP2358
PVC Pipe40Utility 40-/240/120FSP2347
- w Fitting Inside Collar 40Utility 40+-/240/120FSP2333
HDPE Pipe110Utility 100-/240/120FSP2347
HDPE Pipe40Utility 40-/240/120FSP2347
Rehau Raupiano Pipe110Utility 100-/240/120FSP2347
Rehau Raupiano Pipe40Utility 40-/240/120FSP2347
Valsir Triplus Pipe110Utility 100-/240/120FSP2347
Valsir Triplus Pipe40Utility 40-/240/120FSP2358
150mm+ Concrete Slab
PVC (SC) Pipe150Utility 150-/240/180FSP2338
HDPE Pipe160Utility 150-/240/180FSP2366
Rehau Raupiano Pipe160Utility 150-/240/180FSP2366
Valsir Triplus Pipe160Utility 150-/240/180FSP2366
Wall Applications Dia.FRLReport No.
116mm+ Plasterboard Wall *
PVC (SC) Pipe150Utility 150-/120/120FSP2320
PVC (SC) Pipe100Utility 100-/120/120FSP2320
- w Fitting Inside Collar100Utility 100+-/120/120FSP2320
PVC Pipe80Utility 80-/120/120FSP2345
PVC Pipe65Utility 65-/120/120FSP2361
PVC Pipe50Utility 50-/120/120FSP2368
PVC Pipe40Utility 40-/120/120FSP2345
- w Fitting Inside Collar40Utility 40+-/120/120FSP2368
HDPE Pipe160Utility 150-/120/90FSP2368
HDPE Pipe110Utility 100-/120/120FSP2345
HDPE Pipe40Utility 40-/120/120FSP2407
Rehau Raupiano Pipe160Utility 150-/120/120FSP2361
Rehau Raupiano Pipe110Utility 100-/120/120FSP2345
Rehau Raupiano Pipe40Utility 40-/120/120FSP2361
Valsir Triplus Pipe160Utility 150-/120/120FSP2368
Valsir Triplus Pipe110Utility 100-/120/120FSP2345
Valsir Triplus Pipe40Utility 40-/120/120FSP2361
90mm+ Plasterboard Wall **
PVC (SC) Pipe150Utility 150-/60/60
PVC (SC) Pipe100Utility 100-/60/60
- w Fitting Inside Collar100Utility 100+-/60/60
PVC Pipe80Utility 80-/60/60
PVC Pipe65Utility 65-/60/60
PVC Pipe50Utility 50-/60/60
PVC Pipe40Utility 40-/60/60
- w Fitting Inside Collar40Utility 40+-/60/60
HDPE Pipe160Utility 150-/60/60
HDPE Pipe110Utility 100-/60/60
HDPE Pipe40Utility 40-/60/60
Rehau Raupiano Pipe160Utility 150-/60/60
Rehau Raupiano Pipe110Utility 100-/60/60
Rehau Raupiano Pipe40Utility 40-/60/60
Valsir Triplus Pipe160Utility 150-/60/60
Valsir Triplus Pipe110Utility 100-/60/60
Valsir Triplus Pipe40Utility 40-/60/60
75mm+ Hebel Wall (90min)
PVC (SC) Pipe150Utility 150
PVC (SC) Pipe100Utility 100
- w Fitting Inside Collar100Utility 100+
PVC Pipe80Utility 80
PVC Pipe65Utility 65
PVC Pipe50Utility 50
PVC Pipe40Utility 40
- w Fitting Inside Collar40Utility 40+
HDPE Pipe160Utility 150
HDPE Pipe110Utility 100
HDPE Pipe40Utility 40
Rehau Raupiano Pipe160Utility 150
Rehau Raupiano Pipe110Utility 100
Rehau Raupiano Pipe40Utility 40
Valsir Triplus Pipe160Utility 150
Valsir Triplus Pipe110Utility 100
Valsir Triplus Pipe40Utility 40

Tested in Accordance with AS1530.4 & AS4072.1

NCC Compliant for the Above Uses

Product Specs

Concrete Slab, Bondek Slab, Fire-Rated Plasterboard, Concrete and Masonry Wall, 75mm Hebel Powerpanel Wall, 78mm Speedpanel (patched with Fire-rated Plasterboard), Dincel Wall – without removing the plastic, AFS Rediwall – without removing the plastic, AFS Logicwall – without removing fibre sheeting.

Purchase Information

Please contact your local distributor for purchase enquiries. Contact us here.

QLD

Drillfast
Drillfast
www.drillfast.com.au
Email: sales@drillfast.com.au
Phone: 1300 923 414

 


Fyreguard
www.fyreguard.com
Brisbane Phone: (07) 3865 4422
Gold Coast Phone: (07) 5593 4955

 


Global Fasteners www.global-fasteners.com.au

Townsville Phone: (07) 4727 1111
Cairns Phone: (07) 4035 3367
Mackay Phone: (07) 4957 8855
Rockhampton Phone: (07) 4921 0800


VIC


Drillcut
www.drillcut.au
Email: sales@drillcut.com.au
Phone: (03) 8301 9999


ACT

Powagroup
Powagroup
: www.powagroup.com.au
Email: sales@powagroup.com.au
Phone: 1300 303 366


SA

ACURA Group logo
ACURA Group
www.acuragroup.com.au
Email: sales@acuragroup.com.au
Phone: 1300 750 750