MS70C

The MS70C is a plastic, cast-in fire collar for concrete slabs.

Tested and Assessed systems include electrical power cables, insulated copper pipes, as well as data & optical fibre cables. (See below: click on a highlighted report no. to open report).

Click Here for Installation Instructions

Click Here for Drawing

Download Revit file here

Click Here for Recommended Fixings Guide

Click here for Assessment report FCO481

Documentation

Cable and Conduit Details – Separation Active Area to Active Area
ServiceDetailFRL
80mm collar separation40mm collar separation
≥150mm slab≥175mm slab≥150mm slab≥175mm slab
Mix servicesVarious cable combinations from above with or without conduit in the collar.
Only one conduit allowed in the collar.
(Refer to line 1 for conduit details).
-/180/120-/240/120-/180/120-/240/120
One PVC Conduit
(20mm – 50mm nominal)
One empty rigid PVC conduit of (1.6mm to 3mm wall thickness). Minimum 100mm protruding above and below slab.-/180/180-/240/240-/180/120-/240/120
Data and Comms
Cables
(Cat5, Cat5e)
1 to 100 Cables
With or without PVC conduit in the collar.
(Refer to line 1 for conduit details)
-/180/180-/240/240-/180/120-/240/120
Data & Comms Cables
(Cat6, Cat6a, Cat7, RG6)
1 to 80 Cables
With or without PVC conduit in the collar.
(Refer to line 1 for conduit details)
-/180/180-/240/240-/180/120-/240/120
Fibre optic cables
(10.3mm diameter)
1 to full Cables
With or without PVC conduit in the collar.
(Refer to line 1 for conduit details)
-/180/180-/240/240-/180/120-/240/120
Fibre optic cables
(5.3mm diameter)
1 to 10 Cables
With or without PVC conduit in the collar.
(Refer to line 1 for conduit details)
-/180/180-/240/240-/180/120-/240/120
Round insulated copper cables
(2.5mm² to 16mm² 3C+E)
1 to full in collar or in conduit
With PVC conduit in the collar.
(Refer to line 1 for conduit details)
-/180/180-/240/180-/180/120-/240/120
1 to full in collar or in conduit
Without PVC conduit in the collar.
(Refer to line 1 for conduit details)
-/180/120-/240/120-/180/120-/240/120
Flat TPS copper cables
(2.5mm² 2C+E)
1 to 60 Cables
With PVC conduit in the collar.
(Refer to line 1 for conduit details)
-/180/180-/240/240-/180/120-/240/120
1 to 60 Cables
Without PVC conduit in the collar.
(Refer to line 1 for conduit details)
-/180/180-/240/180-/180/120-/240/120
Sealant detailsIn the annular gap between collar opening and cable services or gaps between services not bundled.
When gap ≤5mm: sealant is optional.
When gap ≥ 6mm: Snap Fire Seal FRAS to fill gaps to a minimum depth of 10mm depth and finished off flush with the collar opening
There is no requirement to seal between the conduit and the services passing through the conduit.
Lagged Pipe Details – 80mm Collar Separation – Active Area to Active Area
ServiceSlab ThicknessFRL for each lagging type
PE FoamThermotec
E-Flex ST
K-Flex STSuperMaxArmaflex FRV nitrile rubberActrol SuperPair F/RFoilflex / Sekisui foam Foil- faced
9mm
lagging
9mm
lagging
9-19mm lagging9-19mm lagging9-19mm lagging9-19mm lagging25mm lagging
Paircoil Bundle A
One set of Paircoil (max 3/8" & 3/4”)
with or without any of the following services:
• One of up to 25mm PVC pipe
• One of up to 2.5mm² 2C+E TPS power cable
• One of either
CAT 5, 5e, 6, 6a or 7 cable
≥150mm-/180/90-/180/120-/180/120-/180/120-/180/180-/180/180-/180/120
≥175mm-/240/90-/240/120-/240/120-/240/120-/240/180-/240/180-/180/120
Paircoil Bundle B
One or two sets of Paircoil (max 3/4" & 3/4") with or without any of the following services:
• One of up to 2.5-mm² 2C+E TPS power cables
• One or two of
CAT 5, 5e, 6, 6a or 7 cable
≥150mmN/AN/AN/AN/AN/A-/180/180N/A
≥175mmN/AN/AN/AN/AN/A-/240/180N/A
One of up to 3/4" copper or steel pipe (max 1.2mm wall thickness), with or without a 2.5mm^2 - 2C+E TPS cable≥150mmN/AN/A-/180/120-/180/120-/180/180-/180/180-/180/120
≥175mmN/AN/A-/240/120-/240/120-/240/180-/240/180-/180/120
ServiceSlab ThicknessPE FoamThermotec
E-Flex ST
K-Flex STSuperMaxArmaflex FRV nitrile rubberActrol SuperPair F/RFoilflex / Sekisui foam Foil- faced
N/A9-19mm lagging9-19mm lagging9-19mm lagging9-19mm lagging9-19mm lagging25mm lagging
One of up to 1" copper or steel pipe (max 1.2mm wall thickness), with or without a 2.5mm^2 - 2C+E TPS cable≥150mmN/AN/A-/180/120-/180/120-/180/120N/A-/180/120
≥175mmN/AN/A-/240/120-/240/120-/240/120N/A-/180/120
One lagged PN12 PVC Pipe (16-32mm)≥150mmN/A-/180/180-/180/180-/180/180-/180/180-/180/180-/180/180
≥175mmN/A-/240/240-/240/240-/240/240-/240/240-/240/240-/180/180
Sealant detailsIn the annular gap between collar opening and cable services or gaps between services not bundled.
When gap ≤5mm: sealant is optional.
When gap ≥ 6mm: Snap Fire Seal FRAS to fill gaps to a minimum depth of 10mm depth and finished off flush with the collar opening.
There is no requirement to seal between the conduit and the services passing through the conduit.
Lagged Pipe Details – 40mm Collar Separation – Active Area to Active Area
ServiceSlab ThicknessFRL for each lagging type
PE FoamThermotec
E-Flex ST
K-Flex STSuperMaxArmaflex FRV nitrile rubberActrol SuperPair F/RFoilflex/ Sekisui foam foil-faced
9mm
lagging
9mm
lagging
9-19mm lagging9-19mm lagging9-19mm lagging9-19mm lagging25mm lagging
Paircoil Bundle A
One set of Paircoil (max 3/8" & 3/4”)
with or without any of the following services:
• One of up to 25mm PVC pipe
• One of up to 2.5mm² 2C+E TPS power cable
• One of either
CAT 5, 5e, 6, 6a or 7 cable
≥150mm-/180/90-/180/120-/180/120-/180/120-/180/120-/180/120-/180/120
≥175mm-/240/90-/240/120-/240/120-/240/120-/240/120-/240/120-/240/120
Paircoil Bundle B
One or two sets of Paircoil (max 3/4" & 3/4") with or without any of the following services:
• One of up to 2.5-mm² 2C+E TPS power cables
• One or two of
CAT 5, 5e, 6, 6a or 7 cable
≥150mmN/AN/AN/AN/AN/AN/AN/A
≥175mmN/AN/AN/AN/AN/A-/240/120N/A
One of up to 3/4" copper or steel pipe (max 1.2mm wall thickness), with or without a 2.5mm^2 - 2C+E TPS cable≥150mmN/AN/A-/180/120-/180/120-/180/120-/180/120-/180/120
≥175mmN/AN/A-/240/120-/240/120-/240/120-/240/120-/240/120
ServiceSlab ThicknessPE FoamThermotec
E-Flex ST
K-Flex STSuperMaxArmaflex FRV nitrile rubberActrol SuperPair F/RFoilflex/ Sekisui foam foil-faced
9-19mm lagging9-19mm lagging9-19mm lagging9-19mm lagging9-19mm lagging9-19mm lagging25mm lagging
One of up to 1" copper or steel pipe (max 1.2mm wall thickness), with or without a 2.5mm^2 - 2C+E TPS cable≥150mmN/AN/A-/180/120-/180/120-/180/120N/A-/180/120
≥175mmN/AN/A-/240/120-/240/120-/240/120N/A-/180/120
One lagged PN12 PVC Pipe (16-32mm)≥150mmN/A-/180/120-/180/120-/180/120-/180/120-/180/120-/180/120
≥175mmN/A-/240/120-/240/120-/240/120-/240/120-/240/120-/240/120
Sealant detailsIn the annular gap between collar opening and cable services or gaps between services not bundled.
When gap ≤5mm: sealant is optional.
When gap ≥ 6mm: Snap Fire Seal FRAS to fill gaps to a minimum depth of 10mm depth and finished off flush with the collar opening.
There is no requirement to seal between the conduit and the services passing through the conduit.

 

Product Specs

Element

Cast-In or Retrofit

Application

Pipe Type

, , , , , , ,

Purchase Information

Please contact your local distributor for purchase enquiries. Contact us here.

QLD

Drillfast
Drillfast
www.drillfast.com.au
Email: sales@drillfast.com.au
Phone: 1300 923 414

 


Fyreguard
www.fyreguard.com
Brisbane Phone: (07) 3865 4422
Gold Coast Phone: (07) 5593 4955

 


Global Fasteners www.global-fasteners.com.au

Townsville Phone: (07) 4727 1111
Cairns Phone: (07) 4035 3367
Mackay Phone: (07) 4957 8855
Rockhampton Phone: (07) 4921 0800


VIC


Drillcut
www.drillcut.au
Email: sales@drillcut.com.au
Phone: (03) 8301 9999


ACT

Powagroup
Powagroup
: www.powagroup.com.au
Email: sales@powagroup.com.au
Phone: 1300 303 366


SA

ACURA Group logo
ACURA Group
www.acuragroup.com.au
Email: sales@acuragroup.com.au
Phone: 1300 750 750


You may also like…