Documentation
Stack Applications | Dia. | FRL | Report No. |
150mm+ Concrete Slab | |||
PVC Pipe | 65, 80 | -/240/240 | FAR3933 |
- w Fitting Inside Collar | 65, 80 | -/240/240 | FAR3933 |
P-PVC Pipe | 65, 80 | -/180/180 | FCO3426 |
HDPE Pipe | 63, 75 | -/240/240 | FAR3933 |
Valsir Triplus Pipe | 75 | -/240/240 | FAR3933 |
Wall Applications | Dia. | FRL | Report No. |
128mm Plasterboard Wall * | |||
PVC Pipe | 65, 80, 90 | -/180/120 | FAR3929 |
- w Fitting Inside Collar | 65, 80 | -/180/120 | FAR3929 |
HDPE Pipe | 75, 90 | -/180/120 | FAR3929 |
Rehau Raupiano Pipe | 75 | -/180/120 | FC10394 |
116mm+ Plasterboard Wall ** | |||
PVC Pipe w Fitting Inside Collar | 80 | -/120/120 | FSP2090 |
PVC Pipe w Fitting Inside Collar | 65 | -/120/120 | FSP1902 |
P-PVC Pipe | 65, 80 | -/120/120 | FCO3426 |
96mm+ Plasterboard Wall *** | |||
PVC Pipe | 65, 80, 90 | -/90/60 | FC10395 |
HDPE Pipe | 75 | -/90/60 | FC10395 |
90mm+ Plasterboard Wall **** | |||
PVC Pipe | 65, 80 | -/60/60 | FSP2100 |
FireCrunch MgO Board Wall † | |||
PVC Pipe | 65, 80, 90 | -/90/90 | FCO3268 |
- w Fitting Inside Collar | 65, 80 | -/90/90 | FCO3268 |
HDPE Pipe | 75, 90 | -/90/90 | FCO3268 |
Rehau Raupiano Pipe | 75, 90 | -/90/90 | FCO3268 |
* 2 x 16mm Fire-Rated Plasterboard Sheets Either Side of a 64mm Steel Stud
** 2 x 13mm Fire-Rated Plasterboard Sheets Either Side of a 64mm Steel Stud. For Systems Approved on a 2 x 13mm Fire-rated Plasterboard Sheets One Side of 64mm Steel Stud and 25mm Shaft Liner on the Other, Refer to FCO3348
*** 1 x 16mm Fire-Rated Plasterboard Sheets Either Side of a 64mm Steel Stud
**** 1 x 13mm Fire-Rated Plasterboard Sheets Either Side of a 64mm Steel Stud
† 1 x 10mm Firecrunch MgO Board Either Side of 90mm Steel Stud. Contact Manufacturer for Wall System Details
Tested in Accordance with AS1530.4 & AS4072.1
NCC 2022 Compliant for the Above Uses