Documentation
Stack Applications | Dia. | FRL | Report No. |
150mm+ Concrete Slab | |||
PEX-a Pipe | 32 | -/240/180 | FSP2277 |
PEX-a Pipe | 20, 25 | -/240/240 | FR5670 ††††† |
PEX-a Pipe | 16 | -/240/180 | FR5670 ††††† |
PEX-b Pipe | 16, 20, 25 | -/240/240 | FR5670 ††††† |
+GF+ George Fischer Progef Pipe | 25, 32 | -/240/240 | FSP1657 †††† |
PVC Conduit | 20, 25 | -/240/240 | FSP1781 |
- w 2C+ E Cable | 20, 25 | -/240/240 | FSP1781 |
Plasterboard Ceiling (90min) | |||
PEX-a Pipe | 20 | -/90/90 RISF 60min | FSP2097 |
Wall Applications | Dia. | FRL | Report No. |
128mm+ Plasterboard Wall * | |||
PP-R sdr 7.4 Pipe | 20, 25, 32 | -/180/180 | FAR3929 |
PE sdr 7.4 Pipe | 20, 25, 32 | -/180/180 | FAR3929 |
PEX-a Pipe †† | 32 | -/180/180 | FSP1716 †††† |
PEX-a Pipe | 20, 25 | -/180/180 | FSP1634 †††† |
PEX-a Pipe | 16 | -/180/120 | FSP1634 †††† |
PEX-b Pipe | 25, 32 | -/180/120 | FSP1634 †††† |
PEX-b Pipe | 16, 20 | -/180/180 | FSP1634 †††† |
+GF+George Fischer Progef sdr 11 PN10 Pipe | 20, 25, 32, 40 | -/180/180 | FSP1658 †††† |
+GF+George Fischer Progef sdr 7.4 PN16 Pipe | 20, 25 | -/180/180 | FSP1658 †††† |
116mm+ Plasterboard Wall ** | |||
PVC Conduit | 20, 25 | -/120/120 | FSP1748 |
- w 2C+ E Cable | 20, 25 | -/120/120 | FSP1748 |
- w 12F Optical Fibre Cable | 20 | -/120/120 | FSP1902 |
PVC FlexiPipe | 16 | -/120/120 | FSP1748 |
P-PVC Pipe | 25 | -/120/120 | FSP2237 |
P-PVC Pipe | 15 | -/120/120 | FSP1748 |
C-PVC Pipe | 1 Inch | -/120/120 | FSP2206 |
PEX-a Pipe | 16, 20, 25, 32 | -/120/120 | FSP2206 |
PEX-b Pipe Bundle | 2 X 20 | -/120/120 | FSP1902 |
PX-AL-PX Pipe | 25 | -/120/120 | FSP2206 |
PX-AL-PX Pipe + PEX-b Pipe Bundle | 20 + 20 | -/120/120 | FSP1902 |
96mm+ Plasterboard Wall *** | |||
PVC Pipe | 25, 32 | -/90/60 | FC10395 |
P-PVC Pipe | 20, 25 | -/90/60 | FC10395 |
P-PVC Pipe w Lagging ††† | 15 | -/90/60 | FSP1723 †††† |
PEX-a Pipe ††† | 25, 32 | -/90/60 | FSP1723 †††† |
PEX-a Pipe ††† | 16, 20 | -/90/90 | FSP1723 †††† |
PEX-b Pipe ††† | 16, 20, 25, 32 | -/90/60 | FSP1723 †††† |
90mm+ Plasterboard Wall **** | |||
PVC Conduit | 25 | -/60/60 | FSP2216 |
- w 2C+ E Cable | 25 | -/60/60 | FSP2216 |
- w 12F + 6F Optical Fibre Cable Bundle | 25 | -/60/60 | FSP2216 |
- w Category 7 Cable Bundle | 25 | -/60/60 | FSP2216 |
P-PVC Pipe | 25 | -/60/60 | FSP1985 |
P-PVC Pipe | 20 | -/60/60 | FSP1960 |
P-PVC Pipe | 16 | -/60/60 | FSP1932 |
C-PVC Pipe | 1 Inch | -/60/60 | FSP2188 |
PEX-a Pipe | 16, 25, 32 | -/60/60 | FSP2188 |
PEX-b Pipe | 16, 25 | -/60/60 | FSP1932 |
PEX-b Pipe | 20 | -/60/60 | FSP1985 |
PX-AL-PX Pipe | 25 | -/60/60 | FSP1960 |
PX-AL-PX Pipe | 16, 20 | -/60/60 | FSP1932 |
PX-AL-PE Pipe | 20 | -/60/60 | FSP2188 |
75mm+ Hebel Powerpanel Wall (90 min) | |||
PVC Conduit w 2C + E Cable | 25 | -/90/90 | FSP1807 |
PVC Conduit w 2C + E Cable | 20 | -/90/90 | FSP1783 |
Telstra PVC Conduit | 20 | -/90/90 | FSP1822 |
- w 12F Optical Fibre Cable | 20 | -/90/90 | FSP1822 |
PEX-a Pipe | 16, 20, 25, 32 | -/90/90 | FC10389 |
PEX-b Pipe | 20, 32 | -/90/90 | FSP1807 |
PEX-b Pipe | 25 | -/90/90 | FC10389 |
PEX-b Pipe | 16 | -/90/90 | FSP1783 |
75mm+ Hebel Powerpanel Wall (120 min) | |||
PVC Conduit w 2C+ E Cable | 25 | -/120/120 | FCO3331 |
PVC Conduit | 20 | -/120/120 | FCO3331 |
PEX-a Pipe | 16, 20, 25, 32 | -/120/120 | FC10389 |
PEX-b Pipe | 16, 20, 32 | -/120/120 | FCO3331 |
PEX-b Pipe | 25 | -/120/120 | FC10389 |
FireCrunch MgO Board Wall † | |||
PVC FlexiPipe | 16 | -/90/90 | FCO3268 |
PVC Conduit | 20, 25 | -/90/90 | FCO3268 |
- w 2C+ E Cable | 20, 25 | -/90/90 | FCO3268 |
- w 12F Optical Fibre Cable | 20 | -/90/90 | FCO3268 |
P-PVC Pipe | 15 | -/90/90 | FCO3268 |
PP-R sdr 7.4 Pipe | 20, 25, 32 | -/90/90 | FCO3268 |
PE sdr 7.4 Pipe | 20, 25, 32 | -/90/90 | FCO3268 |
PEX-a Pipe | 16, 20, 25, 32 | -/90/90 | FCO3268 |
PEX-b Pipe | 16, 20, 25, 32 | -/90/90 | FCO3268 |
PEX-b Pipe Bundle | 2 x 20 | -/90/90 | FCO3268 |
PX-AL-PX + PEX-b Pipe Bundle | 20 + 20 | -/90/90 | FCO3268 |
Valsir Pexal Pipe | 15, 20 | -/90/90 | FCO3268 |
+GF+George Fischer Progef sdr 11 PN10 Pipe | 20, 25, 32, 40 | -/90/90 | FCO3268 |
+GF+George Fischer Progef sdr 7.4 PN16 Pipe | 20, 25 | -/90/90 | FCO3268 |
Plastic/Aluminium Composite Pipes | |||
Valsir Pexal Pipe (116mm+ Plasterboard Wall) ** | 20 | -/120/90 | FSP1759 |
Valsir Pexal Pipe (116mm+ Plasterboard Wall) ** | 15 | -/120/120 | FSP1759 |
GasPex PX-AL-PX Pipe (75mm+ Hebel Powerpanel Wall (90min)) | 16, 20 | -/90/90 | FSP2058 |
* 2 x 16mm Fire-rated Plasterboard Sheets Either Side of 64mm Steel Stud
** 2 x 13mm Fire-rated Plasterboard Sheets Either Side of 64mm Steel Stud. For Systems Approved on a 2 x 13mm Fire-rated Plasterboard Sheets One Side of 64mm Steel Stud and 25mm Shaft Liner on the Other, Refer to FCO3348
*** 1 x 16mm Fire-rated Plasterboard Sheets Either Side of 64mm Steel Stud
**** 1 x 13mm Fire-rated Plasterboard Sheets Either Side of 64mm Steel Stud
† 1 x 10mm Firecrunch MgO Board Either Side of 90mm Steel Stud. Contact Manufacturer for Wall System Details
†† Refer to FCO3379 for -/180/180
††† Refer to FCO3379 for -/90/90 and -/90/60
†††† Refer to report in conjunction with FCO3407
††††† Refer to report in conjunction with FC14077
Tested in Accordance with AS1530.4 & AS4072.1
NCC 2022 Compliant for the Above Uses