32R

The 32R is a metal, retrofit fire collar for fire-rated plasterboard, concrete, masonry and Hebel Powerpanel walls and stack applications in concrete floor slabs.

For use with a range of pipe types and diameters (See below: click on a Report No. to Access PDF)

N.B. All Fire Resistance Levels (FRLs) achieved on framed plasterboard wall systems are applicable to concrete or masonry walls of equal or greater thickness (AS1530.4: 2014 Section 10.12.2 (c)).

Click Here for Installation Instructions

Click Here for Drawing

Download Revit file here

Click Here for Recommended Fixings Guide

Documentation

Stack Applications Dia.FRLReport No.
150mm+ Concrete Slab
PEX-a Pipe32-/240/180FSP2277
PEX-a Pipe20, 25-/240/240FR5670 †††††
PEX-a Pipe16-/240/180FR5670 †††††
PEX-b Pipe16, 20, 25-/240/240FR5670 †††††
+GF+ George Fischer Progef Pipe25, 32-/240/240FSP1657 ††††
PVC Conduit20, 25-/240/240FSP1781
- w 2C+ E Cable20, 25-/240/240FSP1781
Plasterboard Ceiling (90min)
PEX-a Pipe20-/90/90
RISF 60min
FSP2097
Wall ApplicationsDia.FRLReport No.
128mm+ Plasterboard Wall *
PP-R sdr 7.4 Pipe20, 25, 32-/180/180FAR3929
PE sdr 7.4 Pipe20, 25, 32-/180/180FAR3929
PEX-a Pipe ††32-/180/180FSP1716 ††††
PEX-a Pipe20, 25-/180/180FSP1634 ††††
PEX-a Pipe16-/180/120FSP1634 ††††
PEX-b Pipe25, 32-/180/120FSP1634 ††††
PEX-b Pipe16, 20-/180/180FSP1634 ††††
+GF+George Fischer Progef sdr 11 PN10 Pipe20, 25, 32, 40-/180/180FSP1658 ††††
+GF+George Fischer Progef sdr 7.4 PN16 Pipe20, 25-/180/180FSP1658 ††††
116mm+ Plasterboard Wall **
PVC Conduit20, 25-/120/120FSP1748
- w 2C+ E Cable20, 25-/120/120FSP1748
- w 12F Optical Fibre Cable20-/120/120FSP1902
PVC FlexiPipe16-/120/120FSP1748
P-PVC Pipe25-/120/120FSP2237
P-PVC Pipe15-/120/120FSP1748
C-PVC Pipe1 Inch-/120/120FSP2206
PEX-a Pipe16, 20, 25, 32-/120/120FSP2206
PEX-b Pipe Bundle2 X 20-/120/120FSP1902
PX-AL-PX Pipe25-/120/120FSP2206
PX-AL-PX Pipe + PEX-b Pipe Bundle20 + 20-/120/120FSP1902
96mm+ Plasterboard Wall ***
PVC Pipe25, 32-/90/60FC10395
P-PVC Pipe20, 25-/90/60FC10395
P-PVC Pipe w Lagging †††15-/90/60FSP1723 ††††
PEX-a Pipe †††25, 32-/90/60FSP1723 ††††
PEX-a Pipe †††16, 20-/90/90FSP1723 ††††
PEX-b Pipe †††16, 20, 25, 32-/90/60FSP1723 ††††
90mm+ Plasterboard Wall ****
PVC Conduit25-/60/60FSP2216
- w 2C+ E Cable25-/60/60FSP2216
- w 12F + 6F Optical Fibre Cable Bundle25-/60/60FSP2216
- w Category 7 Cable Bundle25-/60/60FSP2216
P-PVC Pipe25-/60/60FSP1985
P-PVC Pipe20-/60/60FSP1960
P-PVC Pipe16-/60/60FSP1932
C-PVC Pipe1 Inch-/60/60FSP2188
PEX-a Pipe16, 25, 32-/60/60FSP2188
PEX-b Pipe16, 25-/60/60FSP1932
PEX-b Pipe20-/60/60FSP1985
PX-AL-PX Pipe25-/60/60FSP1960
PX-AL-PX Pipe16, 20-/60/60FSP1932
PX-AL-PE Pipe20-/60/60FSP2188
75mm+ Hebel Powerpanel Wall (90 min)
PVC Conduit w 2C + E Cable25-/90/90FSP1807
PVC Conduit w 2C + E Cable20-/90/90FSP1783
Telstra PVC Conduit20-/90/90FSP1822
- w 12F Optical Fibre Cable20-/90/90FSP1822
PEX-a Pipe16, 20, 25, 32-/90/90FC10389
PEX-b Pipe20, 32-/90/90FSP1807
PEX-b Pipe25-/90/90FC10389
PEX-b Pipe16-/90/90FSP1783
75mm+ Hebel Powerpanel Wall (120 min)
PVC Conduit w 2C+ E Cable25-/120/120FCO3331
PVC Conduit20-/120/120FCO3331
PEX-a Pipe16, 20, 25, 32-/120/120FC10389
PEX-b Pipe16, 20, 32-/120/120FCO3331
PEX-b Pipe25-/120/120FC10389
FireCrunch MgO Board Wall
PVC FlexiPipe16-/90/90FCO3268
PVC Conduit20, 25-/90/90FCO3268
- w 2C+ E Cable20, 25-/90/90FCO3268
- w 12F Optical Fibre Cable20-/90/90FCO3268
P-PVC Pipe15-/90/90FCO3268
PP-R sdr 7.4 Pipe20, 25, 32-/90/90FCO3268
PE sdr 7.4 Pipe20, 25, 32-/90/90FCO3268
PEX-a Pipe16, 20, 25, 32-/90/90FCO3268
PEX-b Pipe16, 20, 25, 32-/90/90FCO3268
PEX-b Pipe Bundle2 x 20-/90/90FCO3268
PX-AL-PX + PEX-b Pipe Bundle20 + 20-/90/90FCO3268
Valsir Pexal Pipe15, 20-/90/90FCO3268
+GF+George Fischer Progef sdr 11 PN10 Pipe20, 25, 32, 40-/90/90FCO3268
+GF+George Fischer Progef sdr 7.4 PN16 Pipe20, 25-/90/90FCO3268
Plastic/Aluminium Composite Pipes
Valsir Pexal Pipe (116mm+ Plasterboard Wall) **20-/120/90FSP1759
Valsir Pexal Pipe (116mm+ Plasterboard Wall) **15-/120/120FSP1759
GasPex PX-AL-PX Pipe (75mm+ Hebel Powerpanel Wall (90min)) 16, 20-/90/90FSP2058

* 2 x 16mm Fire-rated Plasterboard Sheets Either Side of 64mm Steel Stud

** 2 x 13mm Fire-rated Plasterboard Sheets Either Side of 64mm Steel Stud. For Systems Approved on a 2 x 13mm Fire-rated Plasterboard Sheets One Side of 64mm Steel Stud and 25mm Shaft Liner on the Other, Refer to FCO3348

*** 1 x 16mm Fire-rated Plasterboard Sheets Either Side of 64mm Steel Stud

**** 1 x 13mm Fire-rated Plasterboard Sheets Either Side of 64mm Steel Stud

1 x 10mm Firecrunch MgO Board Either Side of 90mm Steel Stud. Contact Manufacturer for Wall System Details

Refer to FCO3379 for -/180/180

†† Refer to FCO3379 for -/90/90 and -/90/60

†††† Refer to report in conjunction with FCO3407

††††† Refer to report in conjunction with FC14077

Tested in Accordance with AS1530.4 & AS4072.1

NCC 2022 Compliant for the Above Uses

Print Friendly, PDF & Email

Product Specs

Element

, , , , , , , ,

Cast-In or Retrofit

Application

,

Pipe Type

, , , , , , , , , , , , ,

Purchase Information

Please contact your local distributor for purchase enquiries. Contact us here.

QLD

Drillfast
Drillfast
www.drillfast.com.au
Email: sales@drillfast.com.au
Phone: 1300 923 414

 


Fyreguard
www.fyreguard.com
Brisbane Phone: (07) 3865 4422
Gold Coast Phone: (07) 5593 4955

 


Global Fasteners www.global-fasteners.com.au

Townsville Phone: (07) 4727 1111
Cairns Phone: (07) 4035 3367
Mackay Phone: (07) 4957 8855
Rockhampton Phone: (07) 4921 0800


VIC


Drillcut
www.drillcut.au
Email: sales@drillcut.com.au
Phone: (03) 8301 9999


ACT

Powagroup
Powagroup
: www.powagroup.com.au
Email: sales@powagroup.com.au
Phone: 1300 303 366


SA

ACURA Group logo
ACURA Group
www.acuragroup.com.au
Email: sales@acuragroup.com.au
Phone: 1300 750 750


Print Friendly, PDF & Email