GAS 50

The Snap GAS 50 is a metal, cast-in or externally mounted collar, and is designed for both wall and floor applications.

For use on plastic/aluminium composite pipes.

Tested on a range of pipe types and diameters (See below: click on a Report No. to access PDF)

N.B. All Fire Resistance Levels (FRLs) achieved on framed plasterboard wall systems are applicable to concrete or masonry walls of equal or greater thickness (AS1530.4: 2014 Section 10.12.2 (c)).

Click Here for Installation Instructions (Mounted)

Click Here for Installation Instructions (Cast-in)

Click Here for Drawing (Mounted)

Click Here for Drawing (Cast-in)

Download Revit file here – GAS50

Download Revit file here – GAS50C

Documentation

Mounted ApplicationsDia.FRLReport No.
Rehau PX-AL-PE
Rehau PX-AL-PE Pipe (Floor) ††40-/240/240FSP1340 †††††
Rehau PX-AL-PE Pipe †††† (128mm+ Plasterboard Wall) **40-/180/180FSP1341 †††††
Rifeng PX-AL-PX
Rifeng PX-AL-PX Pipe * (Floor) ††32, 40, 50-/240/240FCO2719
Rifeng PX-AL-PX Pipe * (128mm+ Plasterboard Wall) **32, 40, 50-/180/180FCO2719
Rifeng PX-AL-PX Pipe * (Masonry or Concrete Wall)32, 40, 50-/180/120FCO2719
Iplex PE-AL-PE
Iplex PE-AL-PE Pipe (Floor) ††32, 40, 50-/240/240FCO2718
Iplex PE-AL-PE Pipe (128mm+ Plasterboard Wall) **32, 40, 50-/180/120FCO2718
Iplex PE-AL-PE Pipe (Concrete or Masonry Wall)32, 40, 50-/180/120FCO2718
Valsir Pexal
Valsir Pexal Pipe (Floor) ††50-/240/180FSP1771
Valsir Pexal Pipe (Floor) ††40-/240/120FSP1758
Valsir Pexal Pipe (116mm+ Plasterboard Wall) ***50-/120/90FSP1759
Valsir Pexal Pipe (116mm+ Plasterboard Wall) ***32, 40-/120/120FSP1759
75mm+ Hebel Powerpanel Wall (90 min)
PX-AL-PX Pipe50-/90/60FSP1807
PX-AL-PX Pipe40-/90/60FC11840
75mm+ Hebel Powerpanel Wall (120 min)
PX-AL-PX Pipe50-/120/60FCO3331
PX-AL-PX Pipe40-/120/60FC11840
FireCrunch MgO Board Wall
Valsir Pexal Pipe32, 40, 50-/90/90FCO3268
Iplex PE-AL-PE Pipe32, 40, 50-/90/90FCO3268
Rifeng PX-AL-PX Pipe32, 40, 50-/90/90FCO3268
Rehau PX-AL-PE Pipe40-/90/90FCO3268
Cast-In Applications (GAS50-C) ††Dia.FRLReport No.
Rehau PX-AL-PE Pipe40-/240/180FSP1340 †††††
Rifeng PX-AL-PX Pipe *50-/240/180FSP1340 †††††
Rifeng PX-AL-PX Pipe * 40-/240/180FSP1340 †††††
Rifeng PX-AL-PX Pipe *32-/240/240FSP1340 †††††
Iplex PE-AL-PE Pipe32-/240/240FCO2718

* Applies to Gaspex, Waterpex, Heatpex, & Chillpex

** 2 x 16mm Fire-rated Plasterboard Sheets Either Side of 64mm Steel Stud

*** 2 x 13mm Fire-rated Plasterboard Sheets Either Side of 64mm Steel Stud. For Systems Approved on a 2 x 13mm Fire-rated Plasterboard Sheets One Side of 64mm Steel Stud and 25mm Shaft Liner on the Other, Refer to FCO3348

1 x 10mm Firecrunch MgO Board Either Side of 90mm Steel Stud. Contact Manufacturer for Wall System Details

†† 150mm+ Thick Concrete Slab

††Modified GAS 50 Collar for Cast-In Applications in 150mm+ Thick Concrete Slab

††Refer to FCO3379 for -/180/180 and -/180/120

††††† Refer to report in conjunction with FCO3407

Tested in Accordance with AS1530.4 & AS4072.1

NCC 2022 Compliant for the Above Uses 

Product Specs

Element

, , , , , , ,

Cast-In or Retrofit

,

Application

Pipe Type

, , , , , , , , ,

Purchase Information

Please contact your local distributor for purchase enquiries. Contact us here.

QLD

Drillfast
Drillfast
www.drillfast.com.au
Email: sales@drillfast.com.au
Phone: 1300 923 414

 


Fyreguard
www.fyreguard.com
Brisbane Phone: (07) 3865 4422
Gold Coast Phone: (07) 5593 4955

 


Global Fasteners www.global-fasteners.com.au

Townsville Phone: (07) 4727 1111
Cairns Phone: (07) 4035 3367
Mackay Phone: (07) 4957 8855
Rockhampton Phone: (07) 4921 0800


VIC


Drillcut
www.drillcut.au
Email: sales@drillcut.com.au
Phone: (03) 8301 9999


ACT

Powagroup
Powagroup
: www.powagroup.com.au
Email: sales@powagroup.com.au
Phone: 1300 303 366


SA

ACURA Group logo
ACURA Group
www.acuragroup.com.au
Email: sales@acuragroup.com.au
Phone: 1300 750 750