Documentation
Mounted Applications | Dia. | FRL | Report No. |
Rehau PX-Al-PE | |||
Rehau PX-AL-PE Pipe (Floor) †† | 32 | -/240/240 | FSP1339 †††† |
Rehau PX-AL-PE Pipe ††† (128mm+ Plasterboard Wall) ** | 16 | -/180/180 | FSP1341 †††† |
Rifeng PX-AL-PX | |||
Rifeng PX-AL-PX Pipe * (Floor) †† | 16, 20, 25, 32 | -/240/240 | FCO2719 |
Rifeng PX-AL-PX Pipe * (128mm+ Plasterboard Wall)** | 16, 20, 25, 32 | -/180/180 | FCO2719 |
Rifeng PX-AL-PX Pipe * (Concrete or Masonry Wall) | 16, 20, 25, 32 | -/180/180 | FCO2719 |
Rifeng PX-AL-PX Pipe * (96mm+ Plasterboard Wall) *** | 20 | -/90/60 | FP5663 ††††† |
Iplex PE-AL-PE | |||
Iplex PE-AL-PE Pipe (Floor) †† | 16, 20, 25, 32 | -/240/240 | FCO2718 |
Iplex PE-AL-PE Pipe ††† (128mm+ Plasterboard Wall) ** | 16 | -/180/180 | FCO2718 |
Iplex PE-AL-PE Pipe (128mm+Plasterboard Wall) ** | 20, 25, 32 | -/180/120 | FCO2718 |
Iplex PE-AL-PE Pipe (Concrete or Masonry Wall) | 16, 20, 25, 32 | -/180/180 | FCO2718 |
Valsir Pexal | |||
Valsir Pexal Pipe (Floor) †† | 15, 20, 26, 32 | -/240/240 | FSP1758 |
Valsir Pexal Pipe (116mm+ Plasterboard Wall) **** | 20, 26 | -/120/120 | FSP1759 |
Valsir Pexal Pipe (116mm+ Plasterboard Wall) **** | 15 | -/120/120 | FSP1759 |
75mm + Hebel Powerpanel Wall (90 min) |
|||
PX-AL-PX Pipe | 20, 25, 32 | -/90/90 | FSP1822 |
PX-AL-PX Pipe | 16 | -/90/90 | FSP1783 |
75mm + Hebel Powerpanel Wall (120 min) |
|||
PX-AL-PX Pipe | 16, 20, 25, 32 | -/120/120 | FCO3331 |
FireCruch MgO Board Wall † | |||
Valsir Pexal Pipe | 15, 20, 26 | -/90/90 | FCO3268 |
Iplex PE-AL-PE Pipe | 16, 20, 25, 32 | -/90/90 | FCO3268 |
Rifeng PX-AL-PX Pipe | 16, 20, 25, 32 | -/90/90 | FCO3268 |
Rehau PX-AL-PE Pipe | 16 | -/90/90 | FCO3268 |
* Applies to Gaspex, Waterpex, Heatpex & Chillpex
** 2 x 16mm Fire-rated Plasterboard Sheets Either Side of 64mm Steel Stud
*** 1 x 16mm Fire-rated Plasterboard Sheets Either Side of 64mm Steel Stud
**** 2 x 13mm Fire-rated Plasterboard Sheets Either Side of 64mm Steel Stud. For Systems Approved on a 2 x 13mm Fire-rated Plasterboard Sheets One Side of 64mm Steel Stud and 25mm Shaft Liner on the Other, Refer to FCO3348
† 1 x 10mm Firecrunch MgO Board Either Side of 90mm Steel Stud. Contact Manufacturer for Wall System Details
†† 150mm+ Thick Concrete Slab
††† Refer to FCO3379 for -/180/180 and -/180/120
†††† Refer to report in conjunction with FCO3407
††††† Refer to report in conjunction with FC14077
Tested in Accordance with AS1530.4 & AS4072.1
NCC 2022 Compliant for the Above Uses