Documentation
Mounted Applications | Dia. | FRL | Report No. |
Rehau PX-AL-PE | |||
Rehau PX-AL-PE Pipe (Floor) †† | 40 | -/240/240 | FSP1340 ††††† |
Rehau PX-AL-PE Pipe †††† (128mm+ Plasterboard Wall) ** | 40 | -/180/180 | FSP1341 ††††† |
Rifeng PX-AL-PX | |||
Rifeng PX-AL-PX Pipe * (Floor) †† | 32, 40, 50 | -/240/240 | FCO2719 |
Rifeng PX-AL-PX Pipe * (128mm+ Plasterboard Wall) ** | 32, 40, 50 | -/180/180 | FCO2719 |
Rifeng PX-AL-PX Pipe * (Masonry or Concrete Wall) | 32, 40, 50 | -/180/120 | FCO2719 |
Iplex PE-AL-PE | |||
Iplex PE-AL-PE Pipe (Floor) †† | 32, 40, 50 | -/240/240 | FCO2718 |
Iplex PE-AL-PE Pipe (128mm+ Plasterboard Wall) ** | 32, 40, 50 | -/180/120 | FCO2718 |
Iplex PE-AL-PE Pipe (Concrete or Masonry Wall) | 32, 40, 50 | -/180/120 | FCO2718 |
Valsir Pexal | |||
Valsir Pexal Pipe (Floor) †† | 50 | -/240/180 | FSP1771 |
Valsir Pexal Pipe (Floor) †† | 40 | -/240/120 | FSP1758 |
Valsir Pexal Pipe (116mm+ Plasterboard Wall) *** | 50 | -/120/90 | FSP1759 |
Valsir Pexal Pipe (116mm+ Plasterboard Wall) *** | 32, 40 | -/120/120 | FSP1759 |
75mm+ Hebel Powerpanel Wall (90 min) |
|||
PX-AL-PX Pipe | 50 | -/90/60 | FSP1807 |
PX-AL-PX Pipe | 40 | -/90/60 | FC11840 |
75mm+ Hebel Powerpanel Wall (120 min) |
|||
PX-AL-PX Pipe | 50 | -/120/60 | FCO3331 |
PX-AL-PX Pipe | 40 | -/120/60 | FC11840 |
FireCrunch MgO Board Wall † | |||
Valsir Pexal Pipe | 32, 40, 50 | -/90/90 | FCO3268 |
Iplex PE-AL-PE Pipe | 32, 40, 50 | -/90/90 | FCO3268 |
Rifeng PX-AL-PX Pipe | 32, 40, 50 | -/90/90 | FCO3268 |
Rehau PX-AL-PE Pipe | 40 | -/90/90 | FCO3268 |
Cast-In Applications (GAS50-C) ††† | Dia. | FRL | Report No. |
Rehau PX-AL-PE Pipe | 40 | -/240/180 | FSP1340 ††††† |
Rifeng PX-AL-PX Pipe * | 50 | -/240/180 | FSP1340 ††††† |
Rifeng PX-AL-PX Pipe * | 40 | -/240/180 | FSP1340 ††††† |
Rifeng PX-AL-PX Pipe * | 32 | -/240/240 | FSP1340 ††††† |
Iplex PE-AL-PE Pipe | 32 | -/240/240 | FCO2718 |
* Applies to Gaspex, Waterpex, Heatpex, & Chillpex
** 2 x 16mm Fire-rated Plasterboard Sheets Either Side of 64mm Steel Stud
*** 2 x 13mm Fire-rated Plasterboard Sheets Either Side of 64mm Steel Stud. For Systems Approved on a 2 x 13mm Fire-rated Plasterboard Sheets One Side of 64mm Steel Stud and 25mm Shaft Liner on the Other, Refer to FCO3348
† 1 x 10mm Firecrunch MgO Board Either Side of 90mm Steel Stud. Contact Manufacturer for Wall System Details
†† 150mm+ Thick Concrete Slab
††† Modified GAS 50 Collar for Cast-In Applications in 150mm+ Thick Concrete Slab
†††† Refer to FCO3379 for -/180/180 and -/180/120
††††† Refer to report in conjunction with FCO3407
Tested in Accordance with AS1530.4 & AS4072.1
NCC 2022 Compliant for the Above Uses