GAS 63

The Snap GAS 63 is a metal, externally mounted collar, and is designed for both wall and floor applications.

For use on plastic/aluminium composite pipes

Tested on a range of pipe brands and diameters. (See below: click on a Report No. to access PDF)

N.B. All Fire Resistance Levels (FRLs) achieved on framed plasterboard wall systems are applicable to concrete or masonry walls of equal or greater thickness (AS1530.4: 2014 Section 10.12.2 (c)).

Click Here for Installation Instructions

Click Here for Drawing

Download Revit file here

Documentation

Mounted ApplicationsDia.FRLReport No.
Rifeng PX-AL-PX Pipe (Floor) 63-/240/240FSP1340 ††
Valsir Pexal Pipe (Floor) 63-/240/120FSP1758
Valsir Pexal Pipe (116mm+ Plasterboard Wall) *63-/120/60FSP1759

* 2 x 13mm Fire-Rated Plasterboard Sheets Either Side of 64mm Steel Stud

150mm+ Thick Concrete Slab

†† Refer to report in conjunction with FCO3407

Tested in Accordance with AS1530.4 & AS4072.1

NCC 2022 Compliant for the Above Uses

Product Specs

Element

, , , ,

Cast-In or Retrofit

Application

Pipe Type

, , , ,

Purchase Information

Please contact your local distributor for purchase enquiries. Contact us here.

QLD

Drillfast
Drillfast
www.drillfast.com.au
Email: sales@drillfast.com.au
Phone: 1300 923 414

 


Fyreguard
www.fyreguard.com
Brisbane Phone: (07) 3865 4422
Gold Coast Phone: (07) 5593 4955

 


Global Fasteners www.global-fasteners.com.au

Townsville Phone: (07) 4727 1111
Cairns Phone: (07) 4035 3367
Mackay Phone: (07) 4957 8855
Rockhampton Phone: (07) 4921 0800


VIC


Drillcut
www.drillcut.au
Email: sales@drillcut.com.au
Phone: (03) 8301 9999


ACT

Powagroup
Powagroup
: www.powagroup.com.au
Email: sales@powagroup.com.au
Phone: 1300 303 366


SA

ACURA Group logo
ACURA Group
www.acuragroup.com.au
Email: sales@acuragroup.com.au
Phone: 1300 750 750