Documentation
Jump to Element
> Concrete or Bondek Slabs
> Plasterboard Lined Steel Stud Walls
Concrete or Bondek Slab – Stack Applications (see Note)
Pipe Dia. (nom mm) | Fitting | Collar | FRL - Slab Thickness | ||
---|---|---|---|---|---|
≥120mm | ≥150mm | ≥175mm | |||
PVC Pipes in Concrete or Bondek Slabs |
|||||
40 | No | Utility 40 | -/120/120 | -/180/180 | -/240/240 |
40 | Yes | Utility 40+ | -/120/120 | -/180/180 | -/240/240 |
50 | No | Utility 50 | -/120/120 | -/180/180 | -/240/240 |
50 | Yes | Utility 50+ | -/120/120 | -/180/180 | -/240/240 |
65 | No | Utility 65 | -/120/120 | -/180/180 | -/240/240 |
65 | Yes | Utility 65+ | -/120/120 | -/180/180 | -/240/240 |
80 | No | Utility 80 | -/120/120 | -/180/180 | -/240/240 |
80 | Yes | Utility 80+ | -/120/120 | -/180/180 | -/240/240 |
90 | No | Utility 80+ | -/120/120 | -/180/180 | -/240/240 |
90 | Yes | Utility 90+ | -/120/120 | -/180/180 | -/240/240 |
100 | No | Utility 100 | -/120/120 | -/180/180 | -/240/240 |
100 | Yes | Utility 100+ | -/120/120 | -/180/180 | -/240/240 |
150 | No | Utility 150 | n/a | -/180/180 | -/240/240 |
HDPE Pipes in Concrete or Bondek Slabs |
|||||
40 | No | Utility 40 | -/120/120 | -/180/180 | -/240/240 |
50 | No | Utility 50 | -/120/120 | -/180/180 | -/240/240 |
56 | No | Utility 50 | -/120/120 | -/180/180 | -/240/240 |
63 | No | Utility 50+ | -/120/120 | -/180/180 | -/240/240 |
75 | No | Utility 65+ | -/120/120 | -/180/180 | -/240/240 |
90 | No | Utility 80+ | -/120/120 | -/180/180 | -/240/240 |
110 | No | Utility 100 | -/120/120 | -/180/180 | -/240/240 |
125 | No | Utility 125 | n/a | -/180/180 | -/240/240 |
160 | No | Utility 150 | n/a | -/180/180 | -/240/240 |
Triplus Pipes in Concrete or Bondek Slabs |
|||||
40 | No | Utility 40 | -/120/120 | -/180/180 | -/240/240 |
50 | No | Utility 50 | -/120/120 | -/180/180 | -/240/240 |
75 | No | Utility 65+ | -/120/120 | -/180/180 | -/240/240 |
90 | No | Utility 80+ | -/120/120 | -/180/180 | -/240/240 |
110 | No | Utility 100 | -/120/120 | -/180/180 | -/240/240 |
160 | No | Utility 150 | n/a | -/180/180 | -/240/240 |
Raupiano Pipes in Concrete or Bondek Slabs |
|||||
40 | No | Utility 40 | -/120/120 | -/180/180 | -/240/240 |
50 | No | Utility 50 | -/120/120 | -/180/180 | -/240/240 |
75 | No | Utility 65+ | -/120/120 | -/180/180 | -/240/240 |
110 | No | Utility 100 | -/120/120 | -/180/180 | -/240/240 |
160 | No | Utility 150 | n/a | -/180/180 | -/240/240 |
For sealing around annular gap see sealant details in FCO3520 | |||||
Note: Snap Fire Seal FRAS to fill Bondek channel underneath collar and 20mm beyond collar (Figure 4 FCO3520) |
Plasterboard Lined Steel Stud Walls
Pipe Dia. (nom) | Fitting | Collar | FRL - Wall Lining | |
---|---|---|---|---|
≥1x13mm Sheets | ≥2x13mm sheets | |||
PVC Pipes in Plasterboard Lined Steel Stud Walls |
||||
40 | No | Utility 40 | -/60/60 | -/120/120 |
40 | Yes | Utility 40+ | -/60/60 | -/120/120 |
50 | No | Utility 50 | -/60/60 | -/120/120 |
50 | Yes | Utility 50+ | -/60/60 | -/120/120 |
65 | No | Utility 65 | -/60/60 | -/120/120 |
65 | Yes | Utility 65+ | -/60/60 | -/120/120 |
80 | No | Utility 80 | -/60/60 | -/120/120 |
80 | Yes | Utility 80+ | -/60/60 | -/120/120 |
90 | No | Utility 80+ | -/60/60 | -/120/120 |
90 | Yes | Utility 90+ | -/60/60 | -/120/120 |
100 | No | Utility 100 | -/60/60 | -/120/120 |
100 | Yes | Utility 100+ | -/60/60 | -/120/120 |
150 | No | Utility 150 | -/60/60 | -/120/120 |
HDPE Pipes in Plasterboard Lined Steel Stud Walls |
||||
40 | No | Utility 40 | -/60/60 | -/120/120 |
50 | No | Utility 50 | -/60/60 | -/120/120 |
56 | No | Utility 50 | -/60/60 | -/120/120 |
63 | No | Utility 50+ | -/60/60 | -/120/120 |
75 | No | Utility 65+ | -/60/60 | -/120/120 |
90 | No | Utility 80+ | -/60/60 | -/120/120 |
110 | No | Utility 100 | -/60/60 | -/120/120 |
125 | No | Utility 125 | n/a | -/120/90 |
160 | No | Utility 150 | n/a | -/120/90 |
Triplus Pipes in Plasterboard Lined Steel Stud Walls |
||||
40 | No | Utility 40 | -/60/60 | -/120/120 |
50 | No | Utility 50 | -/60/60 | -/120/120 |
75 | No | Utility 65+ | -/60/60 | -/120/120 |
90 | No | Utility 80+ | -/60/60 | -/120/120 |
110 | No | Utility 100 | -/60/60 | -/120/120 |
160 | No | Utility 150 | -/60/60 | -/120/120 |
Raupiano Pipes in Plasterboard Lined Steel Stud Walls |
||||
40 | No | Utility 40 | -/60/60 | -/120/120 |
50 | No | Utility 50 | -/60/60 | -/120/120 |
75 | No | Utility 65+ | -/60/60 | -/120/120 |
110 | No | Utility 100 | -/60/60 | -/120/120 |
160 | No | Utility 150 | -/60/60 | -/120/120 |
For sealing around annular gap see sealant details in FCO3520 |
Shaft Liner/Plasterboard Steel Stud Walls
Pipe Dia. (nom) | Fitting | Collar | FRL |
---|---|---|---|
≥2x13mm sheets side one ≥25mm shaft liner side two |
|||
PVC Pipes in Shaft Liner/Plasterboard Steel Stud Walls |
|||
40 | No | Utility 40 | -/120/120 |
40 | Yes | Utility 40+ | -/120/120 |
50 | No | Utility 50 | -/120/120 |
50 | Yes | Utility 50+ | -/120/120 |
65 | No | Utility 65 | -/120/120 |
65 | Yes | Utility 65+ | -/120/120 |
80 | No | Utility 80 | -/120/120 |
80 | Yes | Utility 80+ | -/120/120 |
90 | No | Utility 80+ | -/120/120 |
90 | Yes | Utility 90+ | -/120/120 |
100 | No | Utility 100 | -/120/120 |
100 | Yes | Utility 100+ | -/120/120 |
150 | No | Utility 150 | -/120/120 |
HDPE Pipes in Shaft Liner/Plasterboard Steel Stud Walls |
|||
40 | No | Utility 40 | -/120/120 |
50 | No | Utility 50 | -/120/120 |
56 | No | Utility 50 | -/120/120 |
63 | No | Utility 50+ | -/120/120 |
75 | No | Utility 65+ | -/120/120 |
90 | No | Utility 80+ | -/120/120 |
110 | No | Utility 100 | -/120/120 |
125 | No | Utility 125 | -/120/90 |
160 | No | Utility 150 | -/120/90 |
Triplus Pipes in Shaft Liner/Plasterboard Steel Stud Walls |
|||
40 | No | Utility 40 | -/120/120 |
50 | No | Utility 50 | -/120/120 |
75 | No | Utility 65+ | -/120/120 |
90 | No | Utility 80+ | -/120/120 |
110 | No | Utility 100 | -/120/120 |
160 | No | Utility 150 | -/120/120 |
Raupiano Pipes in Shaft Liner/Plasterboard Steel Stud Walls |
|||
40 | No | Utility 40 | -/120/120 |
50 | No | Utility 50 | -/120/120 |
75 | No | Utility 65+ | -/120/120 |
110 | No | Utility 100 | -/120/120 |
160 | No | Utility 150 | -/120/120 |
For sealing around annular gap see sealant details in FCO3520 |
Hebel or Walsc Walls
Pipe Dia. (nom) | Fitting | Collar | FRL - AAC panel | |
---|---|---|---|---|
75mm Hebel or Walsc (single mesh) | 75mm Hebel (caged mesh) | |||
PVC Pipes in Hebel or Walsc Walls |
||||
40 | No | Utility 40 | -/90/90 | -/120/120 |
40 | Yes | Utility 40+ | -/90/90 | -/120/120 |
50 | No | Utility 50 | -/90/90 | -/120/120 |
50 | Yes | Utility 50+ | -/90/90 | -/120/120 |
65 | No | Utility 65 | -/90/90 | -/120/120 |
65 | Yes | Utility 65+ | -/90/90 | -/120/120 |
80 | No | Utility 80 | -/90/90 | -/120/120 |
80 | Yes | Utility 80+ | -/90/90 | -/120/120 |
90 | No | Utility 80+ | -/90/90 | -/120/120 |
90 | Yes | Utility 90+ | -/90/90 | -/120/120 |
100 | No | Utility 100 | -/90/90 | -/120/120 |
100 | Yes | Utility 100+ | -/90/90 | -/120/120 |
150 | No | Utility 150 | -/90/90 | -/120/90 |
HDPE Pipes in Hebel or Walsc Walls |
||||
40 | No | Utility 40 | -/90/90 | -/120/120 |
50 | No | Utility 50 | -/90/90 | -/120/120 |
56 | No | Utility 50 | -/90/90 | -/120/120 |
63 | No | Utility 50+ | -/90/90 | -/120/120 |
75 | No | Utility 65+ | -/90/90 | -/120/120 |
90 | No | Utility 80+ | -/90/90 | -/120/120 |
110 | No | Utility 100 | -/90/90 | -/120/120 |
125 | No | Utility 125 | -/90/60 | -/120/90 |
160 | No | Utility 150 | -/90/60 | -/120/90 |
Triplus Pipes in Hebel or Walsc Walls |
||||
40 | No | Utility 40 | -/90/90 | -/120/120 |
50 | No | Utility 50 | -/90/90 | -/120/120 |
75 | No | Utility 65+ | -/90/90 | -/120/120 |
90 | No | Utility 80+ | -/90/90 | -/120/120 |
110 | No | Utility 100 | -/90/90 | -/120/120 |
160 | No | Utility 150 | -/90/90 | -/120/120 |
Raupiano Pipes in Hebel or Walsc Walls |
||||
40 | No | Utility 40 | -/90/90 | -/120/120 |
50 | No | Utility 50 | -/90/90 | -/120/120 |
75 | No | Utility 65+ | -/90/90 | -/120/120 |
110 | No | Utility 100 | -/90/90 | -/120/120 |
160 | No | Utility 150 | -/90/90 | -/120/120 |
For sealing around annular gap see sealant details in FCO3520 |
Dincel Wall, AFS Logicwall or AFS Rediwall (see Note)
Pipe Dia. (nom) | Fitting | Collar | FRL - Wall Type | |||
---|---|---|---|---|---|---|
110mm Dincel | 110mm Rediwall | 120mm Logicwall LW120 | 155mm Dincel | |||
PVC Pipes in Dincel Wall, AFS Logicwall or AFS Rediwall |
||||||
40 | No | Utility 40 | -/90/90 | -/90/90 | -/120/120 | -/180/180 |
40 | Yes | Utility 40+ | -/90/90 | -/90/90 | -/120/120 | -/180/180 |
50 | No | Utility 50 | -/90/90 | -/90/90 | -/120/120 | -/180/180 |
50 | Yes | Utility 50+ | -/90/90 | -/90/90 | -/120/120 | -/180/120 |
65 | No | Utility 65 | -/90/90 | -/90/90 | -/120/120 | -/180/180 |
65 | Yes | Utility 65+ | -/90/90 | -/90/90 | -/120/120 | -/180/120 |
80 | No | Utility 80 | -/90/90 | -/90/90 | -/120/120 | -/180/180 |
80 | Yes | Utility 80+ | -/90/90 | -/90/90 | -/120/120 | -/180/120 |
90 | No | Utility 80+ | -/90/90 | -/90/90 | -/120/120 | -/180/180 |
90 | Yes | Utility 90+ | -/90/90 | -/90/90 | -/120/120 | -/180/120 |
100 | No | Utility 100 | -/90/90 | -/90/90 | -/120/120 | -/180/180 |
100 | Yes | Utility 100+ | -/90/90 | -/90/90 | -/120/120 | -/180/120 |
150 | No | Utility 150 | -/90/90 | -/90/90 | -/120/120 | -/180/120 |
HDPE Pipes in Dincel Wall, AFS Logicwall or AFS Rediwall |
||||||
40 | No | Utility 40 | -/90/90 | -/90/90 | -/120/120 | -/180/120 |
50 | No | Utility 50 | -/90/90 | -/90/90 | -/120/120 | -/180/120 |
56 | No | Utility 50 | -/90/90 | -/90/90 | -/120/120 | -/180/120 |
63 | No | Utility 50+ | -/90/90 | -/90/90 | -/120/120 | -/180/120 |
75 | No | Utility 65+ | -/90/90 | -/90/90 | -/120/120 | -/180/120 |
90 | No | Utility 80+ | -/90/90 | -/90/90 | -/120/120 | -/180/120 |
110 | No | Utility 100 | -/90/90 | -/90/90 | -/120/120 | -/180/120 |
125 | No | Utility 125 | -/90/90 | -/90/90 | -/120/90 | -/180/90 |
160 | No | Utility 150 | -/90/90 | -/90/90 | -/120/90 | -/180/90 |
Triplus Pipes in Dincel Wall, AFS Logicwall or AFS Rediwall |
||||||
40 | No | Utility 40 | -/90/90 | -/90/90 | -/120/120 | -/180/120 |
50 | No | Utility 50 | -/90/90 | -/90/90 | -/120/120 | -/180/120 |
75 | No | Utility 65+ | -/90/90 | -/90/90 | -/120/120 | -/180/120 |
90 | No | Utility 80+ | -/90/90 | -/90/90 | -/120/120 | -/180/120 |
110 | No | Utility 100 | -/90/90 | -/90/90 | -/120/120 | -/180/120 |
160 | No | Utility 150 | -/90/90 | -/90/90 | -/120/120 | -/180/120 |
Raupiano Pipes in Dincel Wall, AFS Logicwall or AFS Rediwall |
||||||
40 | No | Utility 40 | -/90/90 | -/90/90 | -/120/120 | -/180/180 |
50 | No | Utility 50 | -/90/90 | -/90/90 | -/120/120 | -/180/180 |
75 | No | Utility 65+ | -/90/90 | -/90/90 | -/120/120 | -/180/180 |
110 | No | Utility 100 | -/90/90 | -/90/90 | -/120/120 | -/180/180 |
160 | No | Utility 150 | -/90/90 | -/90/90 | -/120/120 | -/180/180 |
For sealing around annular gap see sealant details in FCO3520 | ||||||
Note: Fixings to be away from void with a minimum of 25mm embedment into concrete part of the wall. |
Concrete, Masonry and AAC Block Walls
Pipe Dia. (nom) | Fitting | Collar | FRL | |||
---|---|---|---|---|---|---|
Concrete Wall | Masonry wall or AAC block wall | Concrete wall or AAC block wall | Masonry wall | |||
Min 80mm | Min 90mm | Min 120mm | Min 130mm | |||
PVC Pipes in Concrete, Masonry and AAC Block Walls |
||||||
40 | No | Utility 40 | -/60/60 | -/60/60 | -/120/120 | -/120/120 |
40 | Yes | Utility 40+ | -/90/90 | -/90/90 | -/120/120 | -/180/180 |
50 | No | Utility 50 | -/60/60 | -/60/60 | -/120/120 | -/120/120 |
50 | Yes | Utility 50+ | -/90/90 | -/90/90 | -/120/120 | -/180/120 |
65 | No | Utility 65 | -/60/60 | -/60/60 | -/120/120 | -/120/120 |
65 | Yes | Utility 65+ | -/90/90 | -/90/90 | -/120/120 | -/180/120 |
80 | No | Utility 80 | -/60/60 | -/60/60 | -/120/120 | -/120/120 |
80 | Yes | Utility 80+ | -/90/90 | -/90/90 | -/120/120 | -/180/120 |
90 | No | Utility 80+ | -/60/60 | -/60/60 | -/120/120 | -/120/120 |
90 | Yes | Utility 90+ | -/90/90 | -/90/90 | -/120/120 | -/180/120 |
100 | No | Utility 100 | -/60/60 | -/60/60 | -/120/120 | -/120/120 |
100 | Yes | Utility 100+ | -/90/90 | -/90/90 | -/120/120 | -/180/120 |
150 | No | Utility 150 | -/60/60 | -/60/60 | -/120/120 | -/120/120 |
HDPE Pipes in Concrete, Masonry and AAC Block Walls |
||||||
40 | No | Utility 40 | -/60/60 | -/60/60 | -/120/120 | -/120/120 |
50 | No | Utility 50 | -/60/60 | -/60/60 | -/120/120 | -/120/120 |
56 | No | Utility 50 | -/60/60 | -/60/60 | -/120/120 | -/120/120 |
63 | No | Utility 50+ | -/60/60 | -/60/60 | -/120/120 | -/120/120 |
75 | No | Utility 65+ | -/60/60 | -/60/60 | -/120/120 | -/120/120 |
90 | No | Utility 80+ | -/60/60 | -/60/60 | -/120/120 | -/120/120 |
110 | No | Utility 100 | -/60/60 | -/60/60 | -/120/120 | -/120/120 |
125 | No | Utility 125 | -/60/60 | -/60/60 | -/120/90 | -/120/90 |
160 | No | Utility 150 | -/60/60 | -/60/60 | -/120/90 | -/120/90 |
Triplus Pipes in Concrete, Masonry and AAC Block Walls |
||||||
40 | No | Utility 40 | -/60/60 | -/60/60 | -/120/120 | -/120/120 |
50 | No | Utility 50 | -/60/60 | -/60/60 | -/120/120 | -/120/120 |
75 | No | Utility 65+ | -/60/60 | -/60/60 | -/120/120 | -/120/120 |
90 | No | Utility 80+ | -/60/60 | -/60/60 | -/120/120 | -/120/120 |
110 | No | Utility 100 | -/60/60 | -/60/60 | -/120/120 | -/120/120 |
160 | No | Utility 150 | -/60/60 | -/60/60 | -/120/120 | -/120/120 |
Raupiano Pipes in Concrete, Masonry and AAC Block Walls |
||||||
40 | No | Utility 40 | -/60/60 | -/60/60 | -/120/120 | -/120/120 |
50 | No | Utility 50 | -/60/60 | -/60/60 | -/120/120 | -/120/120 |
75 | No | Utility 65+ | -/60/60 | -/60/60 | -/120/120 | -/120/120 |
110 | No | Utility 100 | -/60/60 | -/60/60 | -/120/120 | -/120/120 |
160 | No | Utility 150 | -/60/60 | -/60/60 | -/120/120 | -/120/120 |
For sealing around annular gap see sealant details in FCO3520 |
Speedpanel walls (see Note)
Pipe Dia. (nom) | Fitting | Collar | FRL - Plasterboard Patching | ||
---|---|---|---|---|---|
1 x min. 13mm FR | 1 x min. 16mm FR | 2 x min. 13mm FR |
|||
PVC Pipes in Speedpanel walls |
|||||
40 | No | Utility 40 | -/60/60 | -/90/90 | -/120/120 |
40 | Yes | Utility 40+ | -/60/60 | -/90/90 | -/120/120 |
50 | No | Utility 50 | -/60/60 | -/90/90 | -/120/120 |
50 | Yes | Utility 50+ | -/60/60 | -/90/90 | -/120/120 |
65 | No | Utility 65 | -/60/60 | -/90/90 | -/120/120 |
65 | Yes | Utility 65+ | -/60/60 | -/90/90 | -/120/120 |
80 | No | Utility 80 | -/60/60 | -/90/90 | -/120/120 |
80 | Yes | Utility 80+ | -/60/60 | -/90/90 | -/120/120 |
90 | No | Utility 80+ | -/60/60 | -/90/90 | -/120/120 |
90 | Yes | Utility 90+ | -/60/60 | -/90/90 | -/120/120 |
100 | No | Utility 100 | -/60/60 | -/90/90 | -/120/120 |
100 | Yes | Utility 100+ | -/60/60 | -/90/90 | -/120/120 |
150 | No | Utility 150 | -/60/60 | -/90/90 | -/120/120 |
HDPE Pipes in Speedpanel walls |
|||||
40 | No | Utility 40 | -/60/60 | -/90/90 | -/120/120 |
50 | No | Utility 50 | -/60/60 | -/90/90 | -/120/120 |
56 | No | Utility 50 | -/60/60 | -/90/90 | -/120/120 |
63 | No | Utility 50+ | -/60/60 | -/90/90 | -/120/120 |
75 | No | Utility 65+ | -/60/60 | -/90/90 | -/120/120 |
90 | No | Utility 80+ | -/60/60 | -/90/90 | -/120/120 |
110 | No | Utility 100 | -/60/60 | -/90/90 | -/120/120 |
125 | No | Utility 125 | -/60/60 | -/90/90 | -/120/90 |
160 | No | Utility 150 | -/60/60 | -/90/90 | -/120/90 |
Triplus Pipes in Speedpanel walls |
|||||
40 | No | Utility 40 | -/60/60 | -/90/90 | -/120/120 |
50 | No | Utility 50 | -/60/60 | -/90/90 | -/120/120 |
75 | No | Utility 65+ | -/60/60 | -/90/90 | -/120/120 |
90 | No | Utility 80+ | -/60/60 | -/90/90 | -/120/120 |
110 | No | Utility 100 | -/60/60 | -/90/90 | -/120/120 |
160 | No | Utility 150 | -/60/60 | -/90/90 | -/120/120 |
Raupiano Pipes in Speedpanel walls |
|||||
40 | No | Utility 40 | -/60/60 | -/90/90 | -/120/120 |
50 | No | Utility 50 | -/60/60 | -/90/90 | -/120/120 |
75 | No | Utility 65+ | -/60/60 | -/90/90 | -/120/120 |
110 | No | Utility 100 | -/60/60 | -/90/90 | -/120/120 |
160 | No | Utility 150 | -/60/60 | -/90/90 | -/120/120 |
For sealing around annular gap see sealant details in FCO3520 | |||||
Note: Patching to be 250mm x 250mm plasterboard fixed to wall with 14g-10 65mm Hex-head screws at max 100mm centres |