Documentation
Floorwaste and Shower Applications | Dia. | FRL | Report No. |
120mm+ Concrete Slab | |||
PVC (SC) Pipe | 100 | -/120/120 | FSP2008 |
150mm+ Concrete Slab | |||
PVC (SC) Pipe | 100 | -/240/240 | FCO3426 |
- w Fitting Inside Collar | 100 | -/240/240 | FCO3426 |
PVC Pipe | 50, 65, 80, 100 | -/240/240 | FCO3426 |
- w Fitting Inside Collar | 50, 65, 80, 100 | -/240/240 | FCO3426 |
HDPE Pipe | 110 | -/240/240 | FCO3426 |
HDPE Pipe | 63, 75, 90 | -/240/240 | FAR3932 |
HDPE (Silent) Pipe | 110 | -/240/240 | FAR3932 |
Rehau Raupiano Pipe | 110 | -/240/240 | FCO3426 |
Rehau Raupiano Pipe | 75, 90 | -/240/240 | FC12806 |
Valsir Triplus Pipe | 110 | -/240/240 | FSP1652 |
Akatherm dBlue Pipe* | 110 | -/240/ | FSP1648 |
Side of Concrete Beam | |||
PVC (SC) Pipe w Fitting Inside Collar | 100 | -/240/240 | FCO3426 |
Stack Applications | Dia. | FRL | Report No. |
150mm+ Concrete Slab | |||
PP-R sdr 7.4 Pipe | 50, 63, 75, 90, 110 | -/180/180 | FCO3426 |
PE sdr 7.4 Pipe | 50, 63, 75, 90, 110 | -/180/180 | FCO3426 |
Rehau Raupiano Pipe w Fitting Inside Collar | 75 | -/240/240 | FSP1614 † |
+GF+ Coolfit 2.0 Pipe | d63/110 | -/240/240 | FSP1891 |
* Ask Pipe Manufacturer for Installation Instructions
† Refer to report in conjunction with FCO3407
See Page 8 & 9 of FAR3932: Equivalence of H100FWS-RR and L65FWS, L80FWS & L100FWS Collars
Tested in Accordance with AS1530.4 & AS4072.1
NCC 2022 Compliant for the Above Uses.